Physical Measurement Analysis in Pre-Utility Covid-19 Isolation Room: A Case Study Universitas Mataram Teaching Hospital
Main Authors: | Wardoyo, Eustachius Hagni, Alit, Ida Bagus, Nasrul, Monalisa, Yudhanto, Didit, Fathana, Prima Belia, Saptaningtyas, Rini Srikus |
---|---|
Format: | Article info application/pdf eJournal |
Bahasa: | eng |
Terbitan: |
Rumah Sakit Penyakit Infeksi Prof Dr. Sulianti Saroso
, 2021
|
Subjects: | |
Online Access: |
https://www.ijid-rspisuliantisaroso.co.id/index.php/ijid/article/view/121 https://www.ijid-rspisuliantisaroso.co.id/index.php/ijid/article/view/121/pdf |
ctrlnum |
article-121 |
---|---|
fullrecord |
<?xml version="1.0"?>
<dc schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/ http://www.openarchives.org/OAI/2.0/oai_dc.xsd"><title lang="en-US">Physical Measurement Analysis in Pre-Utility Covid-19 Isolation Room: A Case Study Universitas Mataram Teaching Hospital</title><creator>Wardoyo, Eustachius Hagni</creator><creator>Alit, Ida Bagus</creator><creator>Nasrul, Monalisa</creator><creator>Yudhanto, Didit</creator><creator>Fathana, Prima Belia</creator><creator>Saptaningtyas, Rini Srikus</creator><subject lang="en-US">Negative Pressure Isolation Rooms (NPIRs)</subject><subject lang="en-US">COVID-19</subject><subject lang="en-US">Physical Measurement Analysis</subject><description lang="en-US">Background: Negative pressure room is recommended for the treatment of COVID-19 patients. Aim this study to describe physical measurement analysis of isolation room Universitas Mataram Teaching Hospital. Methods: Newly developed negative pressure isolation room was physical measure using following instruments: anemometer, moisture meter, hygrometer and pressure gauge.  Results: This study showed physical measurement as follow: 1) ACH (air change per hour) 23.3 / hour [minimum: 12+ ACH]; 2) the difference in pressure gradient between the inpatient room and anteroom -30 Pa [minimum -15 Pa]; 3) the mean of air temperature 24.8°C [21-24]; 4) air humidity 58% [maximum 65%] and 5) concrete moisture 22.45%. Conclusion: The COVID-19 isolation room at the Universitas Mataram Teaching Hospital meets the standard criteria.</description><publisher lang="en-US">Rumah Sakit Penyakit Infeksi Prof Dr. Sulianti Saroso</publisher><date>2021-11-26</date><type>Journal:Article</type><type>Other:info:eu-repo/semantics/publishedVersion</type><type>Journal:Article</type><type>File:application/pdf</type><identifier>https://www.ijid-rspisuliantisaroso.co.id/index.php/ijid/article/view/121</identifier><identifier>10.32667/ijid.v7i2.121</identifier><source lang="en-US">The Indonesian Journal of Infectious Diseases; Vol. 7 No. 2 (2021): The Indonesian Journal of Infectious Disease; 1-8</source><source>2599-1698</source><source>2354-6077</source><source>10.32667/ijid.v7i2</source><language>eng</language><relation>https://www.ijid-rspisuliantisaroso.co.id/index.php/ijid/article/view/121/pdf</relation><rights lang="en-US">Copyright (c) 2021 The Indonesian Journal of Infectious Diseases</rights><recordID>article-121</recordID></dc>
|
language |
eng |
format |
Journal:Article Journal Other:info:eu-repo/semantics/publishedVersion Other File:application/pdf File Journal:eJournal |
author |
Wardoyo, Eustachius Hagni Alit, Ida Bagus Nasrul, Monalisa Yudhanto, Didit Fathana, Prima Belia Saptaningtyas, Rini Srikus |
title |
Physical Measurement Analysis in Pre-Utility Covid-19 Isolation Room: A Case Study Universitas Mataram Teaching Hospital |
publisher |
Rumah Sakit Penyakit Infeksi Prof Dr. Sulianti Saroso |
publishDate |
2021 |
topic |
Negative Pressure Isolation Rooms (NPIRs) COVID-19 Physical Measurement Analysis |
url |
https://www.ijid-rspisuliantisaroso.co.id/index.php/ijid/article/view/121 https://www.ijid-rspisuliantisaroso.co.id/index.php/ijid/article/view/121/pdf |
contents |
Background: Negative pressure room is recommended for the treatment of COVID-19 patients. Aim this study to describe physical measurement analysis of isolation room Universitas Mataram Teaching Hospital. Methods: Newly developed negative pressure isolation room was physical measure using following instruments: anemometer, moisture meter, hygrometer and pressure gauge. Results: This study showed physical measurement as follow: 1) ACH (air change per hour) 23.3 / hour [minimum: 12+ ACH]; 2) the difference in pressure gradient between the inpatient room and anteroom -30 Pa [minimum -15 Pa]; 3) the mean of air temperature 24.8°C [21-24]; 4) air humidity 58% [maximum 65%] and 5) concrete moisture 22.45%. Conclusion: The COVID-19 isolation room at the Universitas Mataram Teaching Hospital meets the standard criteria. |
id |
IOS20143.article-121 |
institution |
RSPI Sulianti Saroso Jakarta |
institution_id |
10818 |
institution_type |
library:special library |
library |
Diklat Sulianti Saroso |
library_id |
8009 |
collection |
The Indonesian Journal of Infectious Disease |
repository_id |
20143 |
subject_area |
Kesehatan masyarakat Penyakit Infeksi |
city |
JAKARTA UTARA |
province |
DKI JAKARTA |
repoId |
IOS20143 |
first_indexed |
2024-06-13T07:59:52Z |
last_indexed |
2024-06-13T07:59:52Z |
recordtype |
dc |
_version_ |
1801734881211842560 |
score |
9.9049015 |